INSTRUCTION MANUAL
AM416 Relay Multiplexer
Revision: 2/96
Copyright (c) 1987-1996
Campbell Scientific, Inc.
Zobrazit stránku 0
1 2 3 4 5 6 ... 31 32

Shrnutí obsahu

Strany 1 - INSTRUCTION MANUAL

INSTRUCTION MANUALAM416 Relay MultiplexerRevision: 2/96Copyright (c) 1987-1996Campbell Scientific, Inc.

Strany 2 - Warranty and Assistance

AM416 RELAY MULTIPLEXER4FIGURE 2. Hook-up Diagrams for Datalogger - AM416 ConnectionsCR10(X) Hook-up 21X Hook-upCR7 Hook-upThe 21X or CR7 (with a 7

Strany 3 - TABLE OF CONTENTS

AM416 RELAY MULTIPLEXER5voltage level must fall below 1.5VDC thenexceed 3.5VDC to clock. Pulse width must beat least 5 ms. An additional delay is re

Strany 4

AM416 RELAY MULTIPLEXER6FIGURE 4. Actuation Time of Relays vs.Temperature (oC) and Battery Voltage.4.2 THE MEASUREMENT TERMINALSThe terminals that r

Strany 5 - CAUTIONARY NOTES

AM416 RELAY MULTIPLEXER7(3) Clock/Delay - With the CR10(X), the clockline is connected to a control port. Instruction86 with the pulse port command (

Strany 6

AM416 RELAY MULTIPLEXER8EXAMPLE PROGRAMS - GENERALIZED PROGRAM LOOPS FOR THE CR10(X), 21X AND CR7.21X SAMPLE PROGRAM* 1 Table 1Programs01: 60 Sec.Exec

Strany 7 - AM416 RELAY MULTIPLEXER

AM416 RELAY MULTIPLEXER9FIGURE 7. Wiring Diagram for Strain Gages and Potentiometers(8) Additional Loops - Additional loops may beused if sensors tha

Strany 8 - RELAY MULTIPLEXER

AM416 RELAY MULTIPLEXER10BEGINNING OF POTENTIOMETERMEASUREMENT LOOP06: P87 Beginning of Loop01: 0 Delay02: 6 Loop Count07: P90 Step Loop Index (Extend

Strany 9

AM416 RELAY MULTIPLEXER11FIGURE 8. Single-ended Measurement Without ExcitationFIGURE 9. Differential Measurement Without Excitation6.2 DIFFERENTIAL

Strany 10

AM416 RELAY MULTIPLEXER12FIGURE 10. Half Bridge (Modified 107 Temperature Probe) Hook-up and Measurement.FIGURE 11. Potentiometer Hook-up and Measur

Strany 11

AM416 RELAY MULTIPLEXER13FIGURE 12. Four Wire Half Bridge Hook-up and MeasurementFIGURE 13. Differential Measurement with Sensor Excitation6.4 FULL

Strany 12 - 5. DATALOGGER PROGRAMMING

Warranty and AssistanceThe AM416 RELAY MULTIPLEXER is warranted by CAMPBELLSCIENTIFIC, INC. to be free from defects in materials and workmanship under

Strany 13

AM416 RELAY MULTIPLEXER14FIGURE 14. Full Bridge Measurement with Excitation Compensation6.6 THERMOCOUPLE MEASUREMENTThe datalogger manuals contain t

Strany 14

AM416 RELAY MULTIPLEXER15FIGURE 15. Differential Thermocouple Measurement with Reference Junction at the Datalogger.FIGURE 16. Differential Thermoco

Strany 15

AM416 RELAY MULTIPLEXER166.6.2 SINGLE-ENDED THERMOCOUPLEMEASUREMENTIn single-ended thermocouple measurement,the following precautions must be taken t

Strany 16 - MEASUREMENT EXAMPLES

AM416 RELAY MULTIPLEXER17EXAMPLE PROGRAM - THERMOCOUPLEAND SOIL BLOCK MEASUREMENT(PROGRAM IS FOR CR10(X) - 33LOCATIONS ALLOCATED TO INPUTSTORAGE)* 1 T

Strany 17

AM416 RELAY MULTIPLEXER187. GENERAL MEASUREMENTCONSIDERATIONS1. Long lead lengths - long lead lengthscontribute to the formation of induced andcapac

Strany 18

A-1APPENDIX A. AM416 STUFFING CHART AND SCHEMATICS

Strany 19

APPENDIX A. AM416 STUFFING CHART AND SCHEMATICSA-2

Strany 20

APPENDIX A. AM416 STUFFING CHART AND SCHEMATICSA-3

Strany 21

APPENDIX A. AM416 STUFFING CHART AND SCHEMATICSA-4This is a blank page.

Strany 22

B-1APPENDIX B. DIFFERENCES BETWEEN THE AM416 AND THE AM32The AM416 differs from Campbell Scientific'sAM32 multiplexer in the following ways:1.

Strany 23

iAM416 RELAY MULTIPLEXER MANUALTABLE OF CONTENTSPDF viewers note: These page numbers refer to the printed version of this document. Usethe Adobe Acr

Strany 24 - 8. INSTALLATION

This is a blank page.

Strany 25

This is a blank page.

Strany 26

Campbell Scientific CompaniesCampbell Scientific, Inc. (CSI)815 West 1800 NorthLogan, Utah 84321UNITED [email protected]

Strany 27

ii7. Wiring Diagram for Strain Gages and Potentiometers...98. Single-ended Measurement wit

Strany 28 - This is a blank page

CAUTIONARY NOTESThe AM416 is not designed to multiplex power. Its intended function is to switch low level analogsignals. Switched current in excess

Strany 29

This is a blank page.

Strany 30

1AM416 RELAY MULTIPLEXER1. FUNCTIONThe primary function of the AM416 Multiplexeris to increase the number of sensors that maybe scanned by Campbell&a

Strany 31

AM416 RELAY MULTIPLEXER2Wires from sensors and datalogger areconnected to the gray terminal strips. The setof four terminals located near the strain-

Strany 32 - Campbell Scientific Companies

AM416 RELAY MULTIPLEXER33. AM416 SPECIFICATIONSPOWER*: unregulated 12 VDC (9.6 V to 16 V)- See Figure 4 for implications of low power torelay actuat