Campbell CR7 Manuál s instrukcemi Strana 122

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 186
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 121
SECTION 12. PROGRAM CONTROL INSTRUCTIONS
12-4
12: P89 If X<=>F
01: 25 X Loc DAY
02: 3 >=
03: 6 F
04: 31 Exit Loop if true
13: P95 End
14: P87 Beginning of Loop
01: 1 Delay
02: 0 Loop Count
27: P86 Do
01: 1 Call Subroutine 1
28: P89 If X<=>F
01: 25 X Loc DAY
02: 3 >=
03: 16 F
04: 31 Exit Loop if true
29: P95 End
30: P87 Beginning of Loop
01: 6 Delay
02: 0 Loop Count
36: P86 Do
01: 1 Call Subroutine 1
37: P89 If X<=>F
01: 25 X Loc DAY
02: 3 >=
03: 5 F
04: 32 Exit Loop if false
38: P95 End
39: P End Table 1
* 3 Table 3 Subroutines
01: P85 Beginning of Subroutine
01: 1 Subroutine Number
02: P18 Time
01: 2 Hours into current year
(maximum 8784)
02: 24 Mod/by
03: 25 Loc [:DAY ]
03: P95 End
*** 88 IF X COMPARED TO Y ***
FUNCTION
This instruction compares two input locations
and, if the result is true, executes the specified
Command. The comparison codes are given in
Table 12-5.
PAR. DATA
NO. TYPE DESCRIPTION
01: 4 Input location for X
02: 2 Comparison code (Table 12-5)
03: 4 Input location for Y
04: 2 Command (Table 12-2)
Input locations altered: 0
Execution time: 0.6ms
TABLE 12-5. Comparison Codes
Parameter 1 Function
1IF X = Y
2IF X Y
3IF X Y
4IF X < Y
*** 89 IF X COMPARED TO F ***
FUNCTION
This instruction compares an input location to a
fixed value and, if the result is true, performs
the specified Command. The comparison codes
are given in Table 12-5.
PAR. DATA
NO. TYPE DESCRIPTION
01: 4 Input location for X
02: 2 Comparison code (Table 12-5)
03: FP Fixed value
04: 2 Command (Table 12-2)
*** 90 STEP LOOP INDEX ***
FUNCTION
When used within a Loop (Instruction 87),
Instruction 90 will increment the index counter
by a specified amount after the first time
through the loop, thus affecting all indexed input
location parameters in subsequent instructions
within the loop. For example, if 4 is specified,
the index counter will count up by 4 (0, 4, 8,
12,...) inside the loop. Instruction 90 does not
affect the loop counter which still counts by 1.