4: Do (P86)
1: 41 Set Port 1 High
;CONTROL PORT1 IS CONNECTED WITH A JUMPER TO SW12CTRL
;(SWITCHED 12 VOLT CONTROL)
5: Excitation with Delay (P22)
1: 3 Ex Channel
2: 0 Delay W/Ex (units = 0.01 sec)
3: 10 Delay After Ex (units = 0.01 sec)
4: 0 mV Excitation
;DELAY OF 0.1 SEC TO ALLOW CS500 TO WARM UP AND STABILIZE
;INSTRUCTION (P22) ONLY SERVES FOR DELAYING THE PROGRAM
;NO ACTUAL EXITATION IS NEEDED. E3 IS NOT WIRED
6: Volt (SE) (P1)
1: 1 Reps
2: 5 2500 mV Slow Range
3: 1 SE Channel
4: 1 Loc [ AIR_TEMP ]
5: 0.1 Mult
6: -40 Offset
;TEMPERATURE MEASUREMENT WITH CS500 SENSOR, CONNECTED TO SINGLE
;ENDED CHANNEL 1. TEMPERATURE MEASURED IN DEGREES CELSIUS.
7: Volt (SE) (P1)
1: 1 Reps
2: 5 2500 mV Slow Range
3: 2 SE Channel
4: 2 Loc [ RH ]
5: 0.1 Mult
6: 0.0 Offset
;RELATIVE HUMIDITY MEASUREMENT WITH CS500 SENSOR, CONNECTED TO
;SINGLE ENDED CHANNEL 2. RH MEASURED IN PERCENTAGE.
8: Do (P86)
1: 51 Set Port 1 Low
;SWITCH OFF CS500
9: Volt (Diff) (P2)
1: 1 Reps
2: 2 7.5 mV Slow Range
3: 2 DIFF Channel
4: 3 Loc [ SOLAR_RAD ]
5: 200 Mult
6: 0.0 Offset
;INCOMMING SOLAR RADIATION MEASUREMENT WITH LI200X SENSOR, CONNECTED
;TO DIFFERENTIAL CHANNEL 2.
;THE OUTPUT FROM LI200X IS 0.2 kW/M2, mV. MAXIMUM INCOMING SHORTWAVE SOLAR