PakBus Networking Guide
4
FIGURE 1. PakCom I/O Terminal Screen
• Click on I/O Terminal, click on Open Port, and press the RF400’s
“Program” green button.
• Press “3” to Restore Defaults.
You have just selected (among other things) the default Hopping
Sequence of “0”. It is best to have an ‘unused’ Hopping
Sequence. You can determine if other RF400s near your location
are using a Hopping Sequence by powering down all but one
RF400 (with antenna) and watching for activity in the green LED
over a period of time (close LoggerNet for this test). Other
available Hopping Sequences are 1 to 6. If you select another
Hopping Sequence, set all network radios to the same setting.
• Configure Standby Mode to “< 24 mA always on”
• Leave other settings at defaults (including the Net Address and Radio
Address and leave the Active Interface in “AutoSense” mode).
• Save All Parameters and Exit Setup.
Step 2 – Set up Remote RF400 Series
a. Label the other RF400 “remote”.
b. Restore Default settings.
c. Verify that remote RF400 is set up for the same Hopping Sequence, Net
Address, and Radio Address as the base RF400.