AM16/32B Relay Analog Multiplexer
that only sensor shield (drain) wires be connected to AM16/32B
shield terminals labeled (“
”).
6.1 Single-Ended Analog Measurement without Sensor
Excitation
Sensor to AM16/32B wiring - one single-ended sensor not requiring
excitation can be connected to an input SET with panel mode switch
set to “2x32”.
Multiplexer to Datalogger wiring - The COM signal line is input to a
single-ended analog input channel. The COM signal-ground line is
tied to “
” at the CR23X, 21X, or CR7, and to “AG” at the
CR10(X). Up to 32 single-ended sensors can be measured by one
single-ended datalogger channel in this manner.
Low level single-ended measurements are not
recommended in 21X applications where the 21X's
internal 12VDC supply is used to power the multiplexer
or other peripherals (see Section 4.1.4).
NOTE
50
00 "2 X 32" Mode
COM ODD H
COM ODD L
ODD H
ODD L
(+) SENSOR
(-)
COM
AM16/32
MUXSIGNAL
SHIELD
SENSOR SHIELD
21X/
CR7
CR10(X)
CR23X/CR3000/
CR800/CR850/
CR1000/CR5000
H H H
AG
G
AM16/32B
CABLE3CBL
FIGURE 11. Single-ended Measurement without Excitation
50
00 "4 X 16" Mode
COM ODD H
COM ODD L
ODD H
ODD L
(+) SENSOR
(-)
COM
AM16/32
MUXSIGNAL
SHIELD
SENSOR SHIELD
21X/
CR7
CR10(X)
CR23X/CR3000/
CR800/CR850/
CR1000/CR5000
H H H
L L L
G
AM16/32B
CABLE3CBL
FIGURE 12. Differential Measurement without Excitation
26