TD ADDENDUM—OVERVIEW
AD-OV-4
Key (ID:Data) Explanation
*0 LOG 1 Exit Table 1, enter *0 Mode, compile table and begin
logging.
*6 06:0000 Enter *6 Mode (to view Input Storage).
A 01:21.234 Advance to first storage location. Panel temperature is
21.234°C
(t
he display will show the actual
temperature).
Wait a few seconds:
01:21.423 The CR10X has read the sensor and stored the result
again. The internal tem
p is now 21.423°C. The value
is updated every 5 seconds when the table is executed.
At this point the CR10X is measuring the temperature
every 5 seconds and sending the value to Input
Storage. No data are being saved. The next step is to
have the CR10X send each reading to Final Storage.
*1 01:00 Exit *6 Mode. Enter program table 1.
2A 02:P00 Advance to 2nd instruction location (this is where we
l
eft
off).
84 02:P84 This is the Data Table Instruction.
A 01:0.0000 Enter 84 and advance to the first parameter (which is
the tim
e into the interv
al).
0 01:0 This parameter determines when in the output internal
data is
st
ored. 0 stores data on the even interval.
A 02:0.000 Enter 0 and advance to the second parameter.
0 02:0 This parameter specifies the output interval. 0 stores
data eac
h exec
ution.
A 03:0.0000 Enter 0 and advance to third parameter.
1000 03:1000.00 This parameter specifies how many records to store in
the table bef
ore over
writing the oldest. For this
example, keep 1000 records.
A 03:P00 Enter 1000 and advance to the third program
i
nst
ruction.
70 03:P70 The SAMPLE instruction. It directs the CR10X to take
a r
eading fr
om an Input Storage location and send it to
Final Storage (an Output Processing Instruction).
A 01:0000 Enter 70 and advance to the first parameter
(
repetitions
).
1 01:1 There is only one input location to sample; repetitions = 1.
A 02:0000 Enter 1 and advance to second parameter (Input
Stor
age location to s
ample).
1 02:1 Input Storage Location 1, where the temperature is
s
tor
ed.
A 04:P00 Enter 1 and advance to fourth program instruction.
* 00:00 Exit Table 1.
0 LOG 1 Enter *0 Mode, compile program, log data.