Campbell CR23X Specifikace Strana 339

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 374
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 338
TD ADDENDUM—SECTION 8. PROCESSING AND PROGRAM CONTROL EXAMPLES
AD-8-9
Loop 6, Output every 10 minutes until stopped
by user
17: P87 Beginning of Loop
01: 60 Delay
02: 0 Loop Count
18: P86 Do
01: 1 Call Subroutine 1
19: P91 If Flag/Port
01: 21 Do if flag 1 is low
02: 31 Exit Loop if true
20: P95 End
21: P End Table 1
* 3 Table 3 Subroutines
01: P85 Beginning of Subroutine
01: 1 Subroutine Number
02: P6 Full Bridge
01: 1 Rep
02: 22 7.5 mV 60 Hz rejection Range
03: 1 IN Chan
04: 1 Excite all reps w/EXchan 1
05: 1500 mV Excitation
06: 1 Loc [:LEVEL_FT ]
07: .46199 Mult
08: 102 Offset
03: P84 Data Table
01: 0 Seconds into interval
02: 0 Every time
03: 0 Records (0=auto; -=redirect)
04: P70 Sample
01: 1 Reps
02: 1 Loc LEVEL_FT
05: P95 End
06: P End Table 3
Zobrazit stránku 338
1 2 ... 334 335 336 337 338 339 340 341 342 343 344 ... 373 374

Komentáře k této Příručce

Žádné komentáře